Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 67

Advertising
background image

67

outdoor air dewpoint temperature and will compare this

temperature against the outside air dewpoint temperature

limit configuration (Configuration

ECON

O.DEW). If the

outdoor air dewpoint temperature is greater than O.DEW, free

cooling will not be allowed. Fig. 10 shows a horizontal limit

line in the custom curve of the psychrometric chart. This is the

outdoor air dewpoint limit boundary.
Custom Psychrometric Curves — Refer to the psychrometric

chart and the standard Honeywell A-D curves in Fig. 9. The

curves start from the bottom and rise vertically, angle to the left

and then fold over. This corresponds to the limits imposed by

dry bulb changeover, outdoor enthalpy changeover and

outdoor dewpoint limiting respectively. Therefore, it is now

possible to create any curve desired with the addition of one

outdoor relative humidity sensor and the options for

changeover now available. See Fig. 10 for an example of a

custom curve constructed on a psychrometric chart.
Configuring the Economizer to Communicate Via Actuator

Serial Number — Every actuator used in the Z Series control

system has its own unique serial number. The rooftop control

uses this serial number to communicate with the actuator over

the local equipment network (LEN). These serial numbers are

programmed at the factory and should not need changing.

Should field replacement of an actuator become necessary, it

will be required to configure the serial numbers of the new

actuator. Five individual numbers make up this serial number

and these can be programmed to match the serial number of the

actuator in its Economizer Actuator Configs group, ACT.C

(SN1.1, SN1.2, SN1.3, SN1.4, SN1.5, SN2.1, SN2.2, SN2.3,

SN2.4, SN2.5).
NOTE: The serial numbers for all LEN actuators can be found

inside the control doors of the unit as well as on the actuator

itself. If an actuator is replaced in the field, it is a good idea to

remove the additional peel-off serial number sticker on the

actuator and cover up the old one inside the control doors.

Fig. 10 — Custom Changeover Curve Example

Fig. 9 — Psychrometric Chart for

Enthalpy Control

CONTROL CURVE

CONTROL POINT

(approx Deg) AT 50% RH

A

73

B

68

C

63

D

58

Advertising