Configuration

BP

BF.CF=2

(Modulating Power

Exhaust with Two LEN Actuators Option) — For modulat-

ing exhaust, the Configuration

BP submenu, configure the

following:

Under Configuration

BP

B.V.A the following configu-

rations may be adjusted:

BP.FS

VFD/Act. Fire Speed/Pos.

BP.MN VFD/Act. Min. Speed/Pos.
BP.1M BP 1 Actuator Max Pos.
BP.2M BP 2 Actuator Max Pos.

Configuration

BP

BP.CF=3 (VFD Power Exhaust

Option) — Under Configuration

BP the following configu-

rations may be adjusted:

Under Configuration

BP

B.V.A the following configu-

rations may be adjusted:

BP.FS

VFD/Act. Fire Speed/Pos.

BP.MN VFD/Act. Min. Speed/Pos.
BP.MX VFD Maximum Speed

Configuration

BP

BP.CF=4

(High-Capacity VFD

Power Exhaust) — Under Configuration

BP the following

configurations may be adjusted:

Under Configuration

BP

B.V.A the following configu-

rations may be adjusted:

BP.FS

VFD/Act. Fire Speed/Pos.

BP.MN VFD/Act. Min. Speed/Pos.
BP.MX VFD Maximum Speed
BP.CL

BP Hi Cap VFD Clamp Val.

BP.WT BP Hi Cap VFD Clamp Time

Configuration

BP

BP.CF=5 (Return/Exhaust — Fan

Tracking Control) — Under Configuration

BP the follow-

ing configurations may be adjusted:

BP.SP

Building Pressure Setpt. (see note below)

Under Configuration

BP

B.V.A the following configu-

rations may be adjusted:

BP.FS

VFD/Act. Fire Speed/Pos.

BP.MN VFD/Act. Min. Speed/Pos.
BP.MX VFD Maximum Speed

Under Configuration

BP

FAN.T the following config-

urations may be adjusted:

FT.CF Fan Track Learn Enable (see note below)
FT.TM Fan Track Learn Rate (see note below, not

used when Fan Track Learning is disabled)

FT.ST

Fan Track Initial DCFM

FT.MX Fan Track Max Clamp (see note below, not

used when Fan Track Learning is disabled)

FT.AD Fan Track Max Correction (see note below,

not used when Fan Track Learning is disabled)

FT.OF Fan Track Internl EEPROM (see note below,

not used when Fan Track Learning is disabled)

FT.RM Fan Track Internal Ram (see note below, not

used when Fan Track Learning is disabled)

FT.RS

Fan Track Reset Internal (see note below, not

used when Fan Track Learning is disabled)

SCF.C

Supply Air CFM Config (see note below, not

used when Fan Track Learning is disabled)

NOTE: These configurations are used only if Fan Tracking

learning is enabled. When fan tracking learning is enabled,

the control will add an offset to the Fan Track Initial DCFM

(Configuration

BP

FAN.T

FT.ST) if the building pres-

sure deviates from the Building Pressure Set Point (BP.SP).

Periodically, at the rate set by the Fan Track Learn Rate

(FT.TM) the delta cfm is adjusted upward or downward with a

maximum adjustment at a given instance to be no greater than

Fan Track Max correction (FT.AD). The delta cfm can not

ever be adjusted greater than or less than the Fan Track Max

Clamp (FT.MX).

Set Clock on VFD (If Installed) —

The clock set

mode is used for setting the date and time for the internal clock

of the VFD. In order to use the timer functions of the VFD

control, the internal clock must be set. The date is used to deter-

mine weekdays and is visible in the fault logs. Refer to the

VFD section in Appendix D on page 160 for information on

operating the VFD and using the keypad.

To set the clock, perform the following procedure from the

VFD keypad:

1. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

2. Use the UP or DOWN keys to highlight CLOCK SET on

the display screen and press ENTER (SOFT KEY 2). The

clock set parameter list will be displayed.

3. Use the UP or DOWN keys to highlight CLOCK VISI-

BILITY and press SEL (SOFT KEY 2). This parameter

is used to display or hide the clock on the screen. Use the

UP or DOWN keys to change the parameter setting. Press

OK (SOFT KEY 2) to save the configuration and return

to the Clock Set menu.

4. Use the UP or DOWN keys to highlight SET TIME and

press SEL (SOFT KEY 2). Use the UP or DOWN keys to

change the hours and minutes. Press OK (SOFT KEY 2)

to save the configuration and return to the Clock Set

menu.

5. Use the UP or DOWN keys to highlight TIME FORMAT

and press SEL (SOFT KEY 2). Use the UP or DOWN

keys to change the parameter setting. Press OK (SOFT

KEY 2) to save the configuration and return to the Clock

Set menu.

6. Use the UP or DOWN keys to highlight SET DATE and

press SEL (SOFT KEY 2). Use the UP or DOWN keys to

change the day, month, and year. Press OK (SOFT KEY

2) to save the configuration and return to the Clock Set

menu.

7. Use the UP or DOWN keys to highlight DATE FOR-

MAT and press SEL (SOFT KEY 2). Use the UP or

DOWN keys to change the parameter setting. Press OK

(SOFT KEY 2) to save the configuration and return to the

Clock Set menu.

8. Press EXIT (SOFT KEY 1) twice to return to the main

menu.

BP.SP

Building Pressure Set point

BP.SO

BP Set point Offset

BP.SP

Building Pressure Set point

BP.SO

BP Set point Offset

BP.SP

Building Pressure Set point

BP.SO

BP Set point Offset