PLC inputs/outputs

3/99

11 PLC input s/outputs

The HEIDENHAIN contouring control TNC 416/TNC 406 has a capacity of max. 56 PLC inputs and 31
PLC outputs, the TNC 306 has a capacity of max. 55 PLC inputs and 31 PLC outputs.
These, PLC inputs and PLC outputs can be connected directly to the logic unit.
In addition, one PLC I/O-board PL 410 B, with 64 PLC inputs and 31 PLC outputs, can be connected
to the logic unit.

11.1 Technical data

PLC inputs

PL 410B/logic unit

Potential range:
”1”-signal: Ue

13 V to 30.2 V

”0”-signal: Ue

–20 V to 3.2 V

Current range:
”1”-signal: Ie

3.8 mA to 8.9 mA

”0”-signal: Ie

1.0 mA at Ue = 3.2 V

PLC outputs

Open-collector outputs with current limiting

Logic unit

PL 410B

Min. output potential
for ”1”-signal

3 V below supply voltage

Nominal operating
current per output

0.1 A

1.2 A

Danger to internal components!
Connect inductive loads only with a quenching diode parallel to the inductance.

It is not permissible to short-circuit more than one output from the logic unit simultaneously.
A short-circuit of one output will not cause an overload.