3.5

Usable Devices

3.5.1

SYSMAC-C (when the PLC type setting is SYSMAC-C Series)

Bit Device

Device Name

Device Symbol

Address Range

Read
/Write

Address
Gradual

MICRO/I

PLC

Input/Output Internal Relay

R

CIO

0 - 99915,

120000 - 614315

R/W

Link Relay

LR

LR

0 - 19915

R/W

Holding Relay

HR

HR

0 - 51115

R/W

Auxiliary Memory

Relay

AR

AR

0 - 95915

R

Timer (contact)

TIMC

TC

0 - 2047

R

Counter (contact)

CNTC

TC

0 - 4095

R

Word Device

Device Name

Device Symbol

Address Range

Read
/Write

Address
Gradual

MICRO/I

PLC

Input/Output Internal Relay

WR

CIO

0 - 999, 1200 - 6143

R/W

Link Relay

WLR

LR

0 - 199

R/W

Holding Relay

WHR

HR

0 - 511

R/W

Auxiliary Memory Relay

WAR

AR

0 - 959

R

Timer (current value)

TIMN

TC

0 - 2047

R

Counter (current value)

CNTN

TC

0 - 4095

R

Data Memory

DM

DM

0 - 9999

R/W

Important points to note regarding setting performing Bit Write operations.

With a Bit Write operation, the word data is first read from the PLC, and a logic operation (AND or OR) is performed on
the relevant bit before writing it to the PLC to ensure that the values of other bits in the same channel are preserved. How-
ever, be certain that the PLC does not modify the data in the channel during the time that the MICRO/I is writing the data.