External Device Setup Manual

- FC4 Read input registers - Reading of Input Register (IR) consecutively

- FC5 Write coil - Writing to a single Coil (C)

- FC6 Write single register - Writing to a single Holding Register (HR)

Data sequence of read value

The data sequence for the read value is similar to that of FC1 Read Coils.

Request

Byte 7

FC (Function code)=04

Byte 8-9

Reference No.

Byte 10-11

Number of read words (1 to 125 words)

Normal response

Byte 7

FC (Function code)=04

Byte 8

Number of bytes for the response (number of read words x 2)

From Byte 9

Read data

Abnormal response

Byte 7

FC (Function code)=84 (HEX)

Byte 8

Exception code 01 or 02

Example

Reading of IR300001 (1 word). The read value is 1234 (HEX).

04 00 00 00 01 => 04 02 12 34

Request

Byte 7

FC (Function code)=05

Byte 8-9

Reference No.

Byte 10

Write value (FF when write value is 1, and 00 when write value is 0)

Byte 11

Fixed value 00

Normal response

Byte 7

FC (Function code)=05

Byte 8-9

Reference No.

Byte 10

Write value (FF when write value is 1, and 00 when write value is 0)

Byte 11

Fixed value 00

Abnormal response

Byte 7

FC (Function code)=85 (HEX)

Byte 8

Exception code 01 or 02

Example

Writing of C1 (1 bit). The write value is 1.

05 00 00 FF 00 => 05 00 00 FF 00

Request

Byte 7

FC (Function code) = 06 (HEX)

Byte 8-9

Reference No.

Byte 10-11

Write data