confirm stop command)

recycle condition is present (see

Chilled Water Recycle Mode

section)

time schedule has gone into UNOCCUPIED mode (machine protective limit has been
reached and machine is in alarm)

the start/stop status is overridden to stop from the CCN network or the LID

When a stop signal occurs, the shutdown sequence first stops the compressor by

deactivating the start relay. A status message of ‘‘SHUTDOWN IN PROGRESS,

COMPRESSOR DEENERGIZED’’ is displayed. The guide vanes are then brought to the closed

position. The oil pump relay and the chilled water/brine pump relay are shut down 60 seconds

after the compressor stops. The condenser water pump will be shut down when the

CONDENSER REFRIGERANT TEMP

is less than the

CONDENSER PRESSURE OVERRIDE

minus 5 psi (34 kPa) or is less than or equal to the

ENTERING CONDENSER WATER TEMP

plus 3° F (2° C). The stop-to-start timer will now begin to count down. If the start-to-start timer is

still greater than the value of the start-to-stop timer, then this time is now displayed on the LID.

Certain conditions during shutdown will change this sequence:

if the

COMPRESSOR MOTOR LOAD

is greater than 10% after shutdown, or the

starter contacts remain energized, the oil pump and chilled water pump remain ener-
gized and the alarm is displayed

if the

ENTERING CONDENSER WATER

temperature is greater than 115 F (46 C) at

shutdown, the condenser pump will be deenergized after the 1CR compressor start
relay