D. pre-start alerts, Click here for table 10d — pre-start alerts – Carrier 19XL User Manual

Page 286

Advertising
background image

* [LIMIT] is shown on the LID as temperature, pressure, voltage, etc., predefined or selected by the

operator as an override or an alert.

Table 10D — Prestart Alerts: These alerts only delay start-up. When alert is corrected,
the start-up will continue. No reset is necessary.

Primary Message

Secondary Message

Alarm Message/Primary
Cause

Additional Cause/
Remedy

Prestart Alert

Starts Limit Exceeded

STARTS EXCESSIVE Com-
pressor Starts (8 in 12 hours)

Depress the RESET softkey
if additional start is required.
Reassess start-up require-
ments.

Prestart Alert

High Motor Tempera-
ture

MTRW VALUE exceeded limit
of [LIMIT]*. Check motor tem-
perature.

Check motor cooling line for
proper operation. Check for
excessive starts within a short
time span.

Prestart Alert

High Bearing Tempera-
ture

MTRB VALUE exceeded limit of
[LIMIT]*. Check thrust bearing
temperature.

Check oil heater for proper
operation, check for low oil
level, partially closed oil sup-
ply valves, etc. Check sensor
accuracy.

Prestart Alert

High Discharge Temp

CMPD VALUE exceeded limit of
[LIMIT]*. Check discharge tem-
perature.

Check sensor accuracy. Allow
discharge temperature to
cool. Check for excessive
starts.

Prestart Alert

Low Refrigerant Temp

ERT VALUE exceeded limit of
[LIMIT]*. Check refrigerant tem-
perature.

Check transducer accuracy.
Check for low chilled water/
brine supply temperature.

Prestart Alert

Low Oil Temperature

OILT VALUE exceeded limit of
[LIMIT]*. Check oil temperature.

Check oil heater power, oil
heater relay. Check oil level.

Prestart Alert

Low Line Voltage

V P VALUE exceeded limit of
[LIMIT]*. Check voltage supply.

Check voltage supply. Check
voltage transformers. Consult
power utility if voltage is low.
Adjust voltage potentiometer
in starter for SMM voltage
input.

Prestart Alert

High Line Voltage

V P VALUE exceeded limit of
[LIMIT]*. Check voltage supply.

Check voltage supply. Check
voltage transformers. Consult
power utility if voltage is low.
Adjust voltage potentiometer
in starter for SMM voltage
input.

Prestart Alert

High Condenser Pres-
sure

CRP VALUE exceeded limit of
[LIMIT]*. Check condenser
water and transducer.

Check for high condenser
water temperature. Check
transducer accuracy.