Adding Refrigerant

Follow the procedures described in

Trimming Refrigerant Charge

section.

Removing Refrigerant

If the optional pumpout system is used, the 19XL refrigerant charge may be transferred to a

storage vessel, or within the condenser or cooler. Follow procedures in the

Pumpout and

Refrigerant Transfer Procedures

section when removing refrigerant from the storage tank to the

machine.

Adjusting the Refrigerant Charge

If the addition or removal of refrigerant is required for improved machine performance, follow

the procedures given under the

Trim Refrigerant Charge

section.

Always use the compressor Pumpdown function in the Control Test table to turn
on the evaporator pump and lock out the compressor when transferring refriger-
ant. Liquid refrigerant may flash into a gas and cause possible freeze-up when the
machine pressure is below 65 psig (448 kPa), for HCFC-22, 30 psig (207 kPa) for
HFC-134a.

WARNING

!

WARNING