Table 10C — In Recycle Shutdown

Primary Message

Secondary Message

Probable Cause/Remedy

Recycle Restart Pending

Occupied Mode

Unit in recycle mode, chilled water temperature is not high
enough to start.

Recycle Restart Pending

Remote Contact Closed

Unit in recycle mode, chilled water temperature is not high
enough to start.

Recycle Restart Pending

Start Command In
Effect

Chiller START/STOP on Status01 manually forced to
start, chill water temperature is not high enough to start.

Recycle Restart Pending

Ice Build Mode

Machine in ICE BUILD mode. Chilled Water/Brine Tem-
perature is satisfied for Ice Build Setpoint temperature.