Refrigerant tracer, To pressurize with dry nitrogen – Carrier 19XL User Manual

Page 201

Advertising
background image

Refrigerant Tracer

Use an environmentally acceptable refrigerant as a tracer for leak test procedures.

To Pressurize with Dry Nitrogen

Another method of leak testing is to pressurize with nitrogen only and use a soap bubble

solution or an ultrasonic leak detector to determine if leaks are present. This should only be

done if all refrigerant has been evacuated from the vessel.

1. Connect a copper tube from the pressure regulator on the cylinder to the refrigerant

charging valve. Never apply full cylinder pressure to the pressurizing line. Follow the listed

sequence.

2. Open the charging valve fully.

3. Slowly open the cylinder regulating valve.

4. Observe the pressure gage on the machine and close the regulating valve when the

pressure reaches test level.

Do not exceed

140 psig (965 kPa).

HCFC-22 and HFC-134a should not be mixed with air or oxygen and pressurized
for leak testing. In general, neither refrigerant should not be allowed to be present
with high concentrations of air or oxygen above atmospheric pressures, as the
mixture can undergo combustion.

WARNING

!

WARNING

Advertising