tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of
PVC, PVC/nylon, chrome vinyl or Teflon with a minimum operating temperature range of
–20 C to 60 C is required. See table below for cables that meet the requirements.

When connecting the CCN communication bus to a system element, a color code system for

the entire network is recommended to simplify installation and checkout. The following color
code is recommended:

Manufacturer

Cable No.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

Signal Type

CCN Bus Conductor
Insulation Color

PSIO Module Comm 1
Plug (J5) Pin No.

+

Ground

RED

WHITE

BLACK

1
2
3