mode, and the control will accept modifications from any CCN interface or module
(with the proper authority), as well as the LID. The PIC will use the CCN time sched-
ule to determine start and stop times.

Alarms and Alerts

Alarm (*) and alert (!) status are indicated on the Status tables. An alarm (*) will shut down

the compressor. An alert (!) notifies the operator that an unusual condition has occurred. The

machine will continue to operate when an alert is shown.

Alarms are indicated when the control center alarm light (!) flashes. The primary alarm

message is viewed on the default screen and an additional, secondary, message and

troubleshooting information are sent to the Alarm History table.

When an alarm is detected, the LID default screen will freeze (stop updating) at the time of

alarm. The freeze enables the operator to view the machine conditions at the time of alarm. The

Status tables will show the updated information. Once all alarms have been cleared (by

pressing the RESET softkey), the default LID screen will return to normal operation.

Click here for Figure 13 — LID Default Screen

Click here for Figure 14 — LID Service Screen