g. Open valves 2 and 5.

h. Turn on pumpout condenser water.

i.

Run the pumpout compressor until the storage tank pressure reaches 5 psig (34 kPa)

(18 in. Hg [40 kPa absolute] if repairing the tank).

j.

Turn off the pumpout compressor.

k. Close valves 1a, 1b, 2, 5, and 6.

l.

Turn off pumpout condenser water.