Machine communication wiring, Lead/lag operation – Carrier 19XL User Manual

Page 98

Advertising
background image

chilled water sensor should be installed. If this sensor is not installed, the return chilled water

sensor of the downstream chiller must be relocated to the return chilled water pipe of the

upstream machine.

To properly control the common supply point temperature sensor when chillers are piped in

parallel, the water flow through the shutdown chillers must be isolated so that no water bypass

around the operating chiller occurs. The common point sensor option must not be used if water

bypass around the operating chiller is occurring.

Machine Communication Wiring

Refer to the machine’s Installation Instructions,

Carrier Comfort Network Interface

section for

information on machine communication wiring.

Lead/Lag Operation

The PIC control provides the ability to operate 2 chillers in the LEAD/LAG mode. It also

provides the additional ability to start a designated standby chiller when either the lead or lag

chiller is faulted and capacity requirements are not met. The lead/lag option operates in CCN

mode only. If any other chiller configured for lead/lag is set to the LOCAL or OFF modes, it will

be unavailable for lead/lag operation.

Note: Lead/lag configuration is viewed and edited in Lead/Lag, under the Equipment Configu-

ration table of the Service menu. Lead/lag status during machine operation is viewed in

the MAINT04 table in the Control Algorithm Status table.

Advertising