Transfer Refrigerant from Storage Tank to Machine

1. Equalize refrigerant pressure.

a. Use the Control Test Terminate Lockout to turn on water pumps and monitor pressures.

b. Close pumpout/storage tank valves 2, 4, 5, and 8, and close machine charging valve 7;

open machine isolation valves 11, 12, 13, and 14 (if present).

c. Open pumpout/storage tank valves 3 and 6, open machine valves 1a and 1b.

d. Gradually crack open valve 5 to increase machine pressure to 68 psig (469 kPa) for

HCFC-22, 35 psig (141 kPa) for HFC-134a. Slowly feed refrigerant to prevent freeze up.

Valve

1a

1b

2

3

4

5

6

7

8

11

12

13

14

Condition

C

C

C

C

C

Click here for Figure 36 — 19XL Pumpout Unit Wiring Schematic

Click here for Figure 37 — Optional Pumpout System