Carrier 19XL User Manual

Page 289

Advertising
background image

* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected

by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature,

voltage, etc., at which the control tripped.

Failure To
Start

Starter Transi-
tion Fault

RUN AUX Starter Transition
Fault: Check 1CR/1M/Interlock
mechanism.

Check starter for proper operation. Run
contact failed to close.

Failure To
Start

1CR AUX Con-
tact Fault

1CR AUX Starter Contact
Fault: Check 1CR/1M aux. con-
tacts.

Check starter for proper operation. Start
contact failed to close.

Failure To
Start

Motor Amps Not
Sensed

CA P Motor Amps Not Sensed:
Check motor load signal.

Check for proper motor amps signal to
SMM. Check wiring from SMM to cur-
rent transformer. Check main motor cir-
cuit breaker for trip.

Failure To
Start

Check Refriger-
ant Type

Current Refrigerant Properties
Abnormal — Check Selection of
refrigerant type

Pressures at transducers indicate
another refrigerant type in Control Test.
Make sure to access the ATTACH TO
NETWORK DEVICE table after chang-
ing refrigerant type.

Failure To
Start

Low Oil Pressure

Low Oil Pressure [LIMIT]:
Check oil pressure switch/
pump and 2C aux.

The oil pressure differential switch is
open when the compressor tried to
START. Check the switch for proper
operation. Also, check the oil pump
interlock (2C aux) in the power panel
and the high condenser pressure
switch.

Table 10F — Start-Up Failures: This is an alarm condition. A manual reset is required
to clear. (Continued)

Primary
Message

Secondary
Message

Alarm Message/Primary
Cause

Additional Cause/Remedy