19 function library – Lenze 8400 TopLine User Manual

Page 1501

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

1501

19

Function library

19.1

Function blocks

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01073/1

Setting is bit coded:

Setting

• Lenze setting: 0x02

Bit 0 Setpoint angle without gearbox

factor

0 = Evaluation of the setpoint angle

with gearbox factor.

1 = Evaluation of the setpoint angle

without gearbox factor.

Bit 1 Angle correction with polynomial

0 = Angle correction without

downstream polynomial.

1 = Angle correction with

downstream polynomial.

Bit 2 External angle correction

0 = Internal angle correction

1 = External angle correction

From version 13.00.00

Bit 3 Reserved

...

Bit 7

C01074/1

0

16384 Divisor for actual value zero pulse

• Number of signals to be received

at least until synchronisation gets

active.

• Initialisation: 0 (≡ 1)

Note: The settings 0 and 1 are functionally

identical. If 0 or 1 is set, at least one pulse is

required in order that the synchronisation

gets active.

C01074/2

0

16384 Divisor for setpoint zero pulse

• Number of signals to be received

at least until synchronisation gets

active.

• Initialisation: 0 (≡ 1)

Note: The settings 0 and 1 are functionally

identical. If 0 or 1 is set, at least one pulse is

required in order that the synchronisation

gets active.

Parameter

Possible settings

Info