6.8.3 Troubleshooting the 24 VAC Circuit in FBRA18 Units (Continued)

NOTE: All voltage measurements must be

made within 4 seconds of unit calling for

heat. If unit does not fire within 4 seconds,

ignition modules will lock out and controller

must be turned off then back on to reset.

C

Is 24VAC

present on J1 pin 5

when unit calls for

heat?

Is J1 pin 2

grounded?

Probable cause

is failed interface

board.

Clean lower water

level sensor and

ground it.

Does

CYCLE LED light

when unit calls for

heat?

Go to

"B".

Is 24VAC

present on N/O

terminal of 12VDC

relay?

Is 24VAC

present on COM

terminal of 12VDC relay

when unit calls for

heat?

Probable cause is

failed wiring between

relay and interface

board.

Is

12VDC present

across coil of 12VDC relay

when unit calls for

heat?

Probable cause
is failed 12VDC

relay.

Probable cause is

failed controller wiring

harness or failed

controller.

Probable cause is

failed wiring between

latch relay and 12VDC

relay.

Yes

No

Yes

No

No

Yes

Yes

No

Yes

No

Yes

No