Ac power supply configurations – Juniper Networks MX480 User Manual

Page 67

Advertising
background image

For more information about the AC power specifications, see the

MX480 3D Universal

Edge Router Hardware Guide

.

WARNING:

The router is pluggable type A equipment installed in a

restricted-access location. It has a separate protective earthing terminal
(sized for UNC 1/4-20 ground lugs) provided on the chassis in addition to the
grounding pin of the power supply cord. This separate protective earthing
terminal must be permanently connected to earth.

AC Power Supply Configurations

The MX480 router supports either the low-line (110 V) AC power configuration or the
high-line (220 V) AC power configuration.

In the low-line (110 V) AC power configuration, the MX480 router contains three or
four AC power supplies (see

Figure 21 on page 42

), located horizontally at the rear of

the chassis in slots

PEM0

through

PEM3

(left to right). Each AC power supply provides

power to all components in the router. When three power supplies are present, they
share power almost equally within a fully populated system. Four AC power supplies
provide full power redundancy. If one power supply fails or is removed, the remaining
power supplies assume the entire electrical load without interruption. Three power
supplies provide the maximum configuration with full power for as long as the router
is operational. The low-line configuration requires three power supplies and the fourth
power supply provides redundancy. With high-capacity power supplies, you must have
a minimum of three power supplies installed in the router.

In the high-line (220 V) AC power configuration, the MX480 router contains two or
four AC power supplies (see

Figure 21 on page 42

), located horizontally at the rear of

the chassis in slots

PEM0

through

PEM3

(left to right). In a high-line AC power

configuration, each AC power supply provides power to all components in the router.
When two or more power supplies are present, they share power almost equally within
a fully populated system. Four AC power supplies provide full power redundancy. If
one power supply fails or is removed, the remaining power supplies assume the entire
electrical load without interruption.Two power supplies provide the maximum
configuration with full power for as long as the router is operational. In the two-PEM
high-line configuration, slots

PEM0

and

PEM1

or

PEM2

and

PEM3

are used. The high-line

configuration requires two power supplies, with the third and fourth providing
redundancy. With high-capacity power supplies, you must have a minimum of two
power supplies installed in the router.

Related

Documentation

MX480 Chassis Description on page 7

MX480 Power System Description on page 41

MX480 AC Power Supply LEDs on page 44

43

Copyright © 2013, Juniper Networks, Inc.

Chapter 2: MX480 Hardware Components

Advertising