Function 1: ON-delay

Selection: C04010 = "0" (Lenze setting)

• In this mode, the FB operates like a retriggerable monoflop.

Functional sequence

1. A FALSE-TRUE edge at bIn starts the internal timing element ().
2. After the delay time set via C04011 has elapsed, bOut is set to TRUE.
3. A TRUE-FALSE edge at bIn sets bOut to FALSE again. Simultaneously, the internal timing element

is reset.

5.167.2

Function 2: OFF-delay

Selection: C04010 = "1"

Functional sequence

1. A FALSE-TRUE edge at bIn sets bOut to TRUE. Simultaneously, the internal timing element () is

reset.

2. A TRUE-FALSE edge at bIn starts the internal timing element.
3. After the delay time set via C04011 has elapsed, bOut is reset to FALSE.

= internal timing element

TRUE

FALSE

bOut

t

TRUE

FALSE

bIn

t

C04011

C04011

C04011

t

0

= internal timing element

TRUE

FALSE

bOut

t

TRUE

FALSE

bIn

t

C04011

C04011

C04011

C04011

t

0