2 parameter setting, Parameter setting, 8basic drive functions (mck) – Lenze 8400 StateLine User Manual

Page 405: Danger

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

405

8

Basic drive functions (MCK)

8.4

Holding brake control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.4.2

Parameter setting

How to go to the parameterisation dialog of the holding brake control:

1. »Engineer« Go to the Project view and select the 8400 StateLine controller.
2. Select the Application parameters tab from the Workspace.
3. Go to the Overview dialog level and click the "Basic functions" button.
4. Go to the OverviewBasic functions dialog box and click the Holding brake control button.

Short overview of parameters for holding brake control:

Danger!

A faultless brake control function requires a correct setting of the different deceleration

times in the following parameters!
A wrong setting of the delay times can cause a faulty control of the brake!

Parameter

Info

Lenze setting

Value Unit

C02580

Holding brake: Operating mode

0: Brake control off

C02581/1

Holding brake: Switching threshold

5.00 %

C02581/2

Holding brake: Hyst. release

1.00 %

C02581/3

Holding brake: Hyst. close

1.00 %

C02581/4

Holding brake: FF control starting value 1

0 %

C02581/5

Holding brake: FF control starting value 2

0 %

C02582

Holding brake: Setting

0

Highlighted in grey = display parameter