LU: DC bus undervoltage [xx.0123.00015]

oC1: Power section - short circuit [xx.0123.00016]

oC2: Power section - earth fault [xx.0123.00017]

Response (Lenze setting printed in bold)

Setting:

C00600/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected a DC bus undervoltage. The

inverter control is switched off because the drive

properties of the motor control cannot be provided

anymore due to the DC bus undervoltage.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the

controller inhibit has been switched.

• Switch on mains supply or ensure sufficient supply via

DC bus.

• Adjust setting in

C00142

if required.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised a short circuit of the motor

phases. To protect the device electronics, the inverter

control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If the device is inappropriately dimensioned with

regard to the motor load and the current limitation in

the controller (Imax controller) is set incorrectly, this

error message may also occur.

Motor control: Defining current limits

• Check motor connections and the corresponding plug

connector on the device.

• Only use permissible combinations of device power

and motor power.

• Do not set the dynamics of the current limitation

controller too high.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised an earth fault at one of the

motor phases. To protect the device electronics, the

inverter control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If motor filter, motor cable length, and cable type

(shielding capacity) are dimensioned incorrectly, this

error message may occur due to leakage currents to

PE.

• If motor filters with additional terminals for +UG and

–UG and devices greater or equal 3 kW are used, the

earth fault detection may be triggered due to leakage

currents to +UG and –UG.

• A cause can also be the use of shielded motor cables

longer than 50 m.

• Check motor connections and the corresponding plug

connector on the device.

• Use motor filters, cable lengths, and cable types

recommended by Lenze.

• If motor filters with additional terminals for +UG and

–UG and devices greater or equal 3 kW are used:

up to version V05.00.00:

Set resp. to earth fault

(

C00602

) to "0: No Reaction".

From version V05.01.00 onwards:

Deactivate earth-

fault detection during operation by setting the

filter time (

C01770

) to 250 ms.

• If motor cables longer than 50 m are used:

From version V05.01.00 onwards:

Increase filter

time for earth-fault detection during operation

(

C01770

).