C00106 | auto dcb: hold time, C00107 | dc braking: hold time, C00114 | diginx: inversion – Lenze 8400 StateLine User Manual

Page 622: C00106, C00107, Has expire, C00114, Fter the hold time, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00106

622

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00106

C00107

C00114

Parameter | Name:

C00106 | Auto DCB: Hold time

Data type: UNSIGNED_32

Index: 24469

d

= 5F95

h

Hold time of the automatic DC injection brake

• The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in

C00019

.

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.000 0.500 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00107 | DC braking: Hold time

Data type: UNSIGNED_32

Index: 24468

d

= 5F94

h

Maximum hold time of the manual DC injection brake

• A time can be set here after which the DC injection brake is switched off automatically to prevent the motor from

thermal overload.

• When "999.000 s" is set, the hold time is infinite.

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.000 999.000 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00114 | DigInX: Inversion

Data type: UNSIGNED_16

Index: 24461

d

= 5F8D

h

The polarity of each digital input of the device can be inverted via this bit field.

Digital terminals

Setting range

(min. hex value | max. hex value)

Lenze setting

0x0000

0xFFFF 0x0000 (decimal: 0)

Value is bit-coded: (= bit set)

Info

Bit 0  DI1 inverted

Inversion of digital input 1

Bit 1  DI2 inverted

Inversion of digital input 2

Bit 2  DI3 inverted

Inversion of digital input 3

Bit 3  DI4 inverted

Inversion of digital input 4

Bit 4 

Reserved

Bit 5 

Reserved

Bit 6 

Reserved

Bit 7 

Reserved

Bit 8 

Reserved

Bit 9 

Reserved

Bit 10 

Reserved

Bit 11 

Reserved

Bit 12 

Reserved

Bit 13 

Reserved

Bit 14 

Reserved

Bit 15  CInh inverted

Inversion of digital input RFR (controller enable)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Advertising