4.3

Testing the Cable Hookups

You can check the CT-7000 S3 contact cable connections to the circuit breaker using the steps
below:

a. Start from the “START-UP” menu:

Press the

[5]

key (DIAGNOSTICS).

b. The following screen will be displayed:

Press the

[2]

key (CHECK HOOKUP).

c. The following screen will be displayed:

Make sure the breaker is in the CLOSED position and then press the

[START]

key.

d. The screen will be updated to show the status of each contact as shown:

A report will also be printed on the thermal printer showing the status of each contact.
A contact closure is shown as “C” on the screen and on the printout. An open contact is
shown as “-” on the screen and on the printout.

1 2 3
C - -



"START" TO RETEST
"STOP" TO EXIT

MAKE SURE BREAKER IS
IN CLOSED POSITION

THEN PRESS "START"


1. SLOW CLOSE TEST
2. CHECK HOOKUP
3. TEST TRANSDUCER
4. PRINT DATA
5. ENCODER FILTER
6. CONTACT FILTER

1. TIME BREAKER 09/19/13
2. GET RESULTS 10:10:10
3. SAVE/RESTORE
4. SETUP
5. DIAGNOSTICS