Vanguard CT-7000 S3 User Manual

Page 33

Advertising
background image

REV 1 CT-7000 S3 USER’S MANUAL

28

NOTE

Percentage of stroke is the distance based upon the percentage of the total
breaker’s stroke distance. The distance is always measured from the starting
point at the fully closed position of the breaker contacts.

The following screen will be displayed:

Type the percentage value using the keypad and then press the

[ENTER]

key.

Continue to step e.

2. DIST FROM CLOSE

Press the

[2]

key (DIST FROM CLOSE) to set the open analysis point #1 as a distance

from the contact’s close position.

NOTE

The distance from close range is selectable from 00.0 inch to 99.99 inches or
from 0.0 to 999.0 millimeters. The distance is referenced from the contact’s
closed position.

The following screen will be displayed:

Type the distance value using the keypad and then press the

[ENTER]

key.

Continue to step e.

3. CONTACT #1

Press the

[3]

key (CONTACT #1) to set the open analysis point #1 value equal to the

contact point #1 value. Continue to step e.

NOTE

Contact point #1 is the distance from the contact’s closed position to the
point where it is in transition from the CLOSE to OPEN or the OPEN to CLOSE
position.

OPEN ANALYSIS PT 1

VALUE: 000.0 IN

DISTANCE FROM CLOSE

"ENTER" TO CONFIRM

OPEN ANALYSIS PT 1

%

of total stroke

00

%


"ENTER" TO CONFIRM