REV 1 CT-7000 S3 USER’S MANUAL

118

When performing an OPEN-CLOSE
test, the breaker opens but will not
close.

• Delay between OPEN to CLOSE is probably too short. Increase the

delay time.

No data or erratic reading on travel
transducer.

• Bad transducer. Perform a transducer diagnostic test using the

instructions in section 4.2.

• Transducer slider is not secured to timing rod.
• Transducer is not secured properly.

No activity on “V2” or “V3” voltage
input channel.

• The “V2” and “V3” voltage sensing input channels require a

voltage change greater than 30V.

How do I turn on automatic printing
of test reports?

• Please see section 3.2.3.