Vanguard CT-7000 S3 User Manual

Page 36

Advertising
background image

CT-7000 S3 USER’S MANUAL

REV 1

31

The contact time is printed on the tabulated test results printout in both milliseconds and
cycles. The cycle readings can be in 50 Hz or 60 Hz. You can select the preferred frequency using
the steps below:

a. Start from the “START-UP” menu:

Press the

[4]

key (SETUP).

b. The following screen will be displayed:

Press the

[5]

key (NEXT PAGE).

c. The following screen will be displayed:

Press the

[3]

key (SET 50/60 HZ).

d. The following screen will be displayed:

Press either the

[1]

key (SET 50 Hz) or the

[2]

key (SET 60 Hz) to set the frequency to

the corresponding value.

e. The following confirmation screen will be displayed:

1. SET 50 HZ
2. SET 60 HZ




1. SET DATE & TIME
2. SET PRINT MODE
3. SET 50/60 HZ
4. SET LANGUAGE
5. BLUETOOTH DEV RESET
6. PREVIOUS PAGE

1. ANALYSIS POINTS
2. MEASUREMENT UNITS
3. SHOT DESCRIPTION
4. NUMBER OF CHANNELS
5. NEXT PAGE

1. TIME BREAKER 09/12/13
2. GET RESULTS 10:10:10
3. SAVE/RESTORE
4. SETUP
5. DIAGNOSTICS