CT-7000 S3 USER’S MANUAL

REV 1

69

Enter the end point for the expansion by typing the first digit of the 100 millisecond
increment. For example, to select 900ms, press the

[9]

key. The screen will be

updated as shown:

Press the

[ENTER]

key.

The graph expansion will be printed along with the tabulated test results. You will
be returned to the “START-UP” menu when printing is finished.

4. PLOT 0 – 200MS

Press the

[4]

key (PLOT 0 - 200MS) to print the tabulated test results along with the

graphic test results from 0 – 200 milliseconds. The graph and tabulated results will
be printed on the thermal printer. You will be returned to the “START-UP” menu
when printing is finished. A sample expansion graph from 0-200 ms is shown in
Figure 24.

Figure 22. Typical Tabulated Test Results Printout for a CLOSE Operation

EXPANSION FROM:
900MS

"ENTER" TO CONFIRM