IDEC SmartRelay functions

IDEC SmartRelay Manual

151

Note

Because the FL1E-H12SND does not have a real-time clock, the

seven-day time switch function is not available for this version.

1

Cam

Monday

Wednesday

Tuesday

Saturday

Friday

Thursday

Sunday

1

3

1

2

3

Q

1

1

1

1

Timing diagram (three examples)

Cam 1:

Daily

: 06:30 h to 8:00 h

Cam 2:

Tuesday

: 03:10 h to 04:15 h

Cam 3:

Saturday and Sunday : 16:30 h to 23:10 h

Functional description

Each seven-day time switch has three cams you can use to

configure a time hysteresis. You specify the on- and off-

times at the Cam parameters. The seven-day time switch

sets the output at a certain on-time, if this is not already set.

The seven-day time switch resets the output at a certain off-

time if you configured an off-time, or at the end of the cycle

if you specified a pulse output. You will cause a conflict if the

on- and off-times you set for the seven-day time switch are

identical, though set on different cams. In this case, cam3

takes priority over cam2, whereas cam2 takes priority over

cam1.

The switching state of the seven-day time switch is

determined by the status of all three cams.

Symbol in IDEC

SmartRelay

Wiring

Description

Cam
parameters
1, 2, and 3

At the Cam parameters, you set the
on- and off-times of the seven-day
time switch for each Cam switch.
Here you also configure the days
and the time-of-day.

Par

You specify whether the timer
pulses on for one cycle when
activated and then reset. The pulse
setting applies to all three cams.

Output Q

Q is set when the configured cam is
actuated.

Advertising