Technical data

IDEC SmartRelay Manual

299

A.2 Technical data:

FL1E-H12RCC/FL1E-B12RCC

FL1E-H12RCC

FL1E-B12RCC

Power supply
Input voltage

100...240 V AC/DC

Permissible range

85 ... 265 V AC

100 ... 253 V DC

Permissible mains frequency

47 ... 63 Hz

Power consumption
• 100 V AC
• 240 V AC
• 100 V DC
• 240 V DC

25 ... 40 mA
20 ... 30 mA
10 ... 25 mA
6 ... 15 mA

Inrush current

0.46 A at 100 V DC
0.46 A at 100 V AC
0.92 A at 240 V DC
0.92 A at 240 VAC

Voltage failure buffering
• 100 V AC/DC
• 240 V AC/DC

typ. 10 ms
typ. 20 ms

Power loss at
• 100 V AC
• 240 V AC
• 100 V DC
• 240 V DC

2.8 ... 4.6 VA
4.8 ... 7.2 VA
1.1... 2.9 W
1.4 ... 3.6 W

Backup of the real-time clock at 25

C

typ. 80 hours without battery cartridge

typ. 2 years with battery cartridge

Accuracy of the real-time clock

typ.

2 s / day

Digital inputs
Number

8

Electrical isolation

No

High speed inputs

not applicable for this module

Input frequency
• Normal input
• High speed input

• max. 4 Hz
• not applicable for this module

Input voltage L1
• Signal 0
• Signal 1
• Signal 0
• Signal 1

< 40 V AC
> 79 V AC
< 30 V DC
> 79 V DC