IDEC SmartRelay functions

IDEC SmartRelay Manual

183

• Analog comparator (actual value Ax - Ay, see Chapter

4.4.18)

• Analog trigger (actual value Ax, see Chapter 4.4.16)

• Analog amplifier (actual value Ax, see Chapter 4.4.20)

• Analog multiplexer (actual value AQ, see Chapter 4.4.26)

• Analog ramp control (actual value AQ, see Chapter

4.4.27)

• Analog math (actual value AQ, see Chapter 4.4.30)

• PI controller (actual value AQ, see Chapter 4.4.28)

• Up/down counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number.

Parameter p (number of decimals)

Applies only to the Aen, Ax,

1

and

2

values displayed in a

message text.

Timing diagram

Q

Aen +

1

Ax

En

Aen –

2

Aen

Functional description

A 0 to 1 transition at input En saves the value of the signal at

the analog input Ax. This saved process variable is referred

to as ”Aen”.
Both the analog actual values Ax and Aen are multiplied by

the value at parameter A (gain), and parameter B (offset) is

then added to the product:

(Ax•gain) + offset = Actual value Aen, when input En

changes from 0 to 1, or

(Ax•gain) + offset = Actual value Ax.
Output Q is set when the signal at input En = 1 and if the

actual value at input Ax is out of range of

Aen -

2

to Aen +

1

.

Output Q is reset, when the actual value at input Ax lies

within the range of

Aen -

2

to Aen+

1

, or when the signal at

input En changes to lo.