IDEC FL1E SmartRelay User Manual

Page 234

Advertising
background image

IDEC SmartRelay functions

220

IDEC SmartRelay Manual

Note

For further information on the controller basics please refer to the
online help for WindLGC.

The updated value PV is used to calculate in the formulas:

Updated value PV = (PV•gain) + offset

• If the updated value PV = SP, then the special function

does not change the value of AQ.

• Dir = upwards (+) (timing diagram numbers 1. and 3.)

- If the updated value PV > SP, then the special function

reduces the value of AQ.

- If the updated value PV < SP, then the special function

increases the value of AQ.

• Dir = downwards (-) (timing diagram number 2.)

- If the updated value PV > SP, then the special function

increases the value of AQ.

- If the updated value PV < SP, then the special function

reduces the value of AQ.

With a disturbance, AQ continues to increase / decrease

until the updated value PV again corresponds to SP. The

speed with which AQ changes depends on the parameters

KC and TI.
If the input PV exceeds the parameter Max, then the updated

value PV is set to the value of Max. If the PV falls short of the

parameter Min, then the updated value PV is set to the value

of Min.
If the input R is set to 1, then the AQ output is reset. As long

as R is set, the input A/M is disabled.

Sampling time

The sampling time is fixed at 500 ms.

Parameter sets

For more information and application examples with

application-related parameter sets for KC, TI and Dir refer to

the online help for WindLGC.