IDEC SmartRelay functions

IDEC SmartRelay Manual

179

Setting the Par parameter

The gain and offset parameters are used to adapt the

sensors to the relevant application.
View in programming mode:

B3 1+
On

=+00000

Off =+00000

Parameter protection mode

On threshold
Off threshold

Press

B3 2
A

=00.00

B

=+00000

p

=0

Gain

Offset

Decimals in the message text

Example

In a heating control system, the supply T

v

and return line

temperatures T

r

are to be compared, for example with a

sensor at AI2.
A control signal is to be triggered (for example ”heater On”)

when the difference between the supply and return line

temperatures is greater than 15

. The control signal is reset

when the difference is less than 5

C.

The process variable of the temperature is to be shown in

parameter assignment mode.
The thermocouples available have the the following

technical data: -30 to +70

C, 0 to 10 VDC.

Application

Internal mapping

-30 to +70

C = 0 to 10 V DC

0 to 1000

0

C

300

Offset = -30

Range of values:
-30 to +70

C = 100

1000

Gain = 100/1000 = 0.1

On threshold = 15

C

Threshold = 15

Off threshold = 5

C

Threshold = 5

See also Chapter 4.3.6.