IDEC SmartRelay functions

IDEC SmartRelay Manual

213

Parameter

Level 1 and Level 2:

Levels to be reached

Range of values for each level:

-10,000 to +20,000

MaxL:

Maximum value that must not be
exceeded under any
circumstances.

Range of values:

-10,000 to +20,000

StSp:

Start/Stop offset:

value that is added to Offset ”B”
to create the start/stop level. If the
Start/Stop offset is 0, then the
start/stop level is Offset ”B”..

Range of values:

0 to +20,000

Rate:

Acceleration with which level 1,
level 2 or Offset is reached.

Steps/seconds are issued.

Range of values:

1 to 10,000

A: Gain

Range of values: 0 to 10.00

B: Offset

Range of values:

10,000

p: Number of decimals

Range of values: 0, 1, 2, 3

Output AQ The output AQ is scaled using the

formula:

Range of values for AQ:

0 to +32767
(Current Level - Offset ”B”)/ Gain ”A”

Range of values:

0 to +32767
Note:

When AQ is displayed in parameter
mode or message mode, it is
displayed as an unscaled value
(engineering units: current level).

Symbol in IDEC

SmartRelay

Wiring

Description