background image

IDEC SmartRelay installation and wiring

IDEC SmartRelay Manual

55

IDEC SmartRelay expansion modules, operating states

IDEC SmartRelay expansion modules have three operating

states: The LED (RUN/STOP) is lit green, red or orange.

CM AS Interface, communication states

The CM AS Interface has three communication states: The

LED is lit green, red or flashes red/yellow.

CM AS Interface, behavior on communication failure

• If the AS Interface voltage fails, communication between

the IDEC SmartRelay system and the expansion

modules, which are arranged to the right of the IDEC

SmartRelay CM AS Interface expansion module, is

interrupted.

Recommendation: Position IDEC SmartRelay CM AS

Interface on the far right side.

• If communication is interrupted, the switching outputs are

reset after about 40 to 100 ms.

LED (RUN/STOP) is lit

Green (RUN)

Red (STOP)

Orange/Yellow

The expansion module
communicates with the
device to the left.

The expansion module
does not communicate
with the device to its
left.

Initialization phase of
the expansion module

LED AS-I is lit

Green

Red

Red/Yellow

AS Interface
communication OK

AS Interface
communication failed

Slave has address ”0”.