IDEC FL1E SmartRelay User Manual

Page 183

Advertising
background image

Q

Off = 5

f

a

= 9

f

a

= 10

f

a

= 8

f

a

= 5

G_T

Fre

On = 9

f

a

= Input frequency

IDEC SmartRelay functions

IDEC SmartRelay Manual

169

Timing diagram

Functional description

The frequency trigger measures the signals at input Fre. The

pulses are recorded across a configurable time G_T.
Output Q is set and reset in accordance with the set

thresholds. See the calculation rule below.

Calculation rule

• If the On threshold

 Off threshold, then:

Q = 1, if f

a

> On

Q = 0, if f

a

≦ Off.

• If the On threshold < Off threshold, then:

Q = 1, if On ≦ f

a

< Off.

Setting the Par parameter

Note

The system scans the counter limit value once per interval G_T.

View in programming mode (example):

B15 1+
On

=0009

Off =0005

Parameter protection mode
On threshold

Off threshold

Press

B15 2
G_T=01:00s

Time interval for pulses

(example)

Advertising