1 connectors, Connectors, Programming idec smartrelay – IDEC FL1E SmartRelay User Manual

Page 72: 58 idec smartrelay manual, Inputs outputs analog inputs

Advertising
background image

AI4

1 2 1 2

1 2 1 2

L+ M I13I14 I15 I16

Q11

Q9

Q12

Q10

RUN/STOP

L+ M

AI5

RUN/STOP

L+ M AI3

I3 I4

I5 I6

Q1

Q2

Q3

Q4

AI1 AI2

L+ M I9 I10 I11I12

Q7

Q5

Q8

Q6

RUN/STOP

M3U3AI6M4 U4

1 2 1 2

1 2 1 2 1 2 1 2

1 2 1 2

PE

INPUT 2x (..10 V/..20 mA)

L+ M

Inputs

Outputs

Analog inputs

Programming IDEC SmartRelay

58

IDEC SmartRelay Manual

3.1 Connectors

IDEC SmartRelay is equipped with inputs and outputs

Example of a configuration with several modules:

Each input is identified by the letter I plus a number. When

you look at IDEC SmartRelay from the front, you can see the

input terminals at the top. Only analog modules FL1B-J2B2

have the inputs at the bottom.

Each output is identified by the letter Q plus a number

(FL1D-K2B2, FL1D-K2BM2: AQ plus number). In the figure,

you can see the output terminals at the bottom.

Note

IDEC SmartRelay can recognize, read and switch the I/O of all

expansion modules regardless of their type. The I/Os are presented

in the installation order of the modules.

The following I/Os and marker blocks are available for creating your

circuit program: : I1 to I24, AI1 to AI8, Q1 to Q16, AQ1 and AQ2,

M1 to M27 and AM1 to AM6. Also available are the shift register bits
S1 to S8, 4 cursor keys: C , C , C and C , four function keys
on the Text Display: F1, F2, F3, and F4 as well as 16 blank outputs

X1 to X16. See Chapter 4.1 for more details.

The following applies to inputs I1, I2, I7 and I8 of FL1E-H12RCE/

FL1E-B12RCE and FL1E-H12SND versions: If you use I1, I2, I7 or

I8 in the circuit program, this input signal is digital. If you use AI3,

AI4, AI1, or AI2, the input signal is analog. The numbering of the

analog inputs is significant: AI1 and AI2 corresponded to I7 and I8

on the FL1D module. With the addition of two new analog inputs for

the FL1E series, these modules optionally use I1 for AI3 and I2 for

AI4. See the graphical representation at 2.1.1. Also note that you

can also use I3, I4, I5, and I6 as fast digital inputs.

The illustration above with numbered AI inputs shows the

conceptual usage of the inputs, not the actual physical

markings on the module.

Advertising