A.11 technical data: fl1d-k2b2, fl1d-k2bm2, Technical data – IDEC FL1E SmartRelay User Manual

Page 333

Advertising
background image

Technical data

IDEC SmartRelay Manual

319

A.11 Technical data:

FL1D-K2B2, FL1D-K2BM2

(1) Voltage output: If short-circuit protection or overcurrent protection is activated for a

voltage output, the error limit of the other voltage is not ensured.

FL1D-K2B2

FL1D-K2BM2

Power supply
Input voltage

24 V DC

24 V DC

Permissible range

20.4 ... 28.8 V DC

20.4 ... 28.8 V DC

Power consumption

25 ...50 mA

35 ...90 mA

Voltage failure buffering

typ. 5 ms

typ. 5 ms

Power loss at 24 V

0.6 ... 1.2 W

0.9 ... 2.2 W

Electrical isolation

No

No

Reverse polarity protection

Yes

Yes

Ground terminal

for connecting ground
and shielding of the
analog output line.

for connecting ground
and shielding of the
analog output line.

Analog outputs
Number

2

2

Voltage range

0 ... 10 V DC

0 ... 10 V DC

Voltage load

>= 5 k

>= 5 k

Current output

-

0/4 ... 20 mA

Current load

-

<= 250

Resolution

10 bit, normalized to 0 ...
1000

10 bit, normalized to 0 ...
1000

Cycle time for analog output

depending on installation
(typ. 50 ms)

depending on installation
(typ. 50 ms)

Electrical isolation

No

No

Line length (shielded and
twisted)

10 m

10 m

Error limit

Voltage output:

+/- 2.5 % at full scale

Voltage output:

+/- 2.5 % at full scale
Current output:

+/- 3 % at full scale

Short circuit protection

Yes

Yes

Response at short-circuit

(1)

(1)

Overload protection

Yes

Yes

Response at overload

(1)

(1)

Advertising