IDEC SmartRelay functions

IDEC SmartRelay Manual

175

Parameter p (number of decimals)

Does not apply to the display of On, Off and Ax values in a

message text.

Timing diagram A: Function with negative difference

Q

O

n

Ax

Off = On +

Timing diagram B: Function with positive difference

Q

Off = On +

Ax

On

Functional description

The function fetches the analog signal at input Ax.
Ax is multiplied by the value of the A (gain) parameter, and

the value at parameter B (offset) is added to product, i.e.

(Ax•gain) + offset = actual value of Ax.
Output Q is set or reset, depending on the set (On) thresold

and difference value (

). The function automatically

calculates the Off parameter: Off = On +

, whereby  may

be positive or negative. See the calculation rule below.

Calculation rule

• When you set a negative differential value

, the On

threshold

 Off threshold, and:

Q = 1, if the actual value Ax > On

Q = 0, if the actual value Ax

 Off. 

See the timing diagram A.

• When you set a positive differential value

, the On

threshold < the Off threshold, and Q = 1, if:

On

 actual value Ax < Off.

See the timing diagram B.