Technical data

316

IDEC SmartRelay Manual

Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp
ballasts must also be considered. If the maximum allowed surge current is exceeded,
fluorescent lamps must be switched with appropriate contactor relays.

(1): 8 V DC (Version 1 to 5 specifications)
(2): 1.0 mA (Version 1 to 5 specifications)

Short circuit-proof cos 0.5 to 0.7

Power protection B16,
900A

Power protection B16,
900A

Parallel output circuits for power
increase

Not permitted

Not permitted

Protection of output relay

(if desired)

max. 16 A,
characteristic B16

max. 16 A,
characteristic B16

Minimum Switching Load

10 mA, 12 V DC

10 mA, 12 V DC

Initial Contact Resistance

100 m

maximum

(at 1A, 24V DC)

100 m

 maximum

(at 1A, 24V DC)

Mechanical Life

10,000,000

operations minimum

(no load, 10 Hz)

10,000,000

operations minimum

(no load, 10 Hz)

Electrical Life

100,000 operations
minimum (rated
resistive load, 1800
operations / hour)

100,000 operations
minimum (rated
resistive load, 1800
operations / hour)

Switching rate
Mechanical

10 Hz

10 Hz

Ohmic load/lamp load

2 Hz

2 Hz

Inductive load

0.5 Hz

0.5 Hz

FL1E-H12RCE

FL1E-B12RCE

FL1B-M08B2R2