IDEC FL1E SmartRelay User Manual

Page 180

Advertising
background image

IDEC SmartRelay functions

166

IDEC SmartRelay Manual

Functional description

The operating hours counter monitors input En. When En =

1, IDEC SmartRelay computes the time expired and the

time-to-go MN. IDEC SmartRelay shows these times in

parameter assignment mode. Output Q is set when the time-

to-go MN = 0.
A signal at reset input R resets output Q and sets the preset

value of MI at the counter for the duration of MN. The

operating hours counter OT is not affected.
With a signal at the reset input Ral, you reset output Q and

set the preset value of MI at the counter for the duration of

MN. The operating hours counter OT is reset to zero.
Depending on your configuration of parameter Q, the output

is either reset with a signal at input

R or Ral (”Q

0:R”), or when a reset signal is set hi, or the

En signal is set lo (”Q

0:R+En”).

Viewing the MI, MN and OT values

In WindLGC you can fetch the hours counter via the "Tools

-> Transfer: Hours counter" menu command.

Limit value of OT

The value of the operating hours in OT are retained when

you reset the hours counter with a signal at input R. The

hours counter OT will be reset to zero with a transition from

0 to 1 at Ral. The hours counter OT continues the count as

long as En = 1, irrespective of the status at the reset input R.

The counter limit of OT is 99999 h. The hours counter stops

when it reaches this value.
In programming mode, you can set the initial value of OT.

MN is calculated according to the following formula when

reset input R never enabled: MN = MI - (OT % MI).
Example:

0

Hours

20

40

60

80

100

120

MN

OT

30h

30h

30h

30h

20h

100h

MI

MI = 30h, OT = 100h

MN = 30 - (100 % 30)

MN = 30 -10

MN = 20h

In runtime mode, the value OT can not be preset. If the value

for MI is changed, there would be no calculation for the MN.

MN will take on the value of MI.

Advertising