IDEC SmartRelay functions

178

IDEC SmartRelay Manual

Parameter p (number of decimals)

Does not apply to Ax, Ay, On, Off and

 values displayed in

a message text.

Does not apply to the comparison of on and off values! (The

compare function ignores the decimal point.)

Q

for Ax - Ay > 200,
if On = Off = 200

Ax

1000

0

Ay

1000

0

Ax - Ay

1000

0

200

Timing diagram

Functional description

The function fetches the analog values from the inputs Ax

and Ay.
Ax and Ay are each multiplied by the value of the A (gain)

parameter, and the value at parameter B (offset) is then

added to the relevant product, i.e.

(Ax•gain) + offset = actual value Ax or

(Ay•gain) + offset = actual value Ay.
The function forms the difference (”

”) between the actual

values Ax - Ay.
Output Q is set or reset, depending on difference of the

actual values Ax - Ay and the set thresholds. See the

calculation rule below.

Calculation rule

• If the On threshold

 Off threshold, then:

Q = 1, if:

(actual value Ax - actual value Ay) > On

Q = 0, if:

(actual value Ax - actual value Ay)

 Off.

• If the On threshold < Off threshold, then Q = 1, if:

On

 (actual value Ax - actual value Ay) < Off.