2. An analog value of 300 (range 0...1000) as the value for

Ax must be modulated to a digital signal string. The user-

defined T (periodic time) parameter is 10 seconds. At the

digital output of the PWM function the digital signal string

is 3 seconds high, 7 seconds low, 3 seconds high, 7

seconds low and continues in that pattern as long as

parameter ”En” = high.

Calculation rule

Q = 1, for (Ax - Min)/ (Max - Min) of time period T, when Min

< Ax < Max

Q = 0, for PT - [ (Ax - Min) / (Max - Min) ] of time period T.

Note

Ax in this calculation refers to the actual value Ax as calculated
using the Gain and Offset.

Setting the Par Parameter

The following illustration shows the view in programming

mode that corresponds to the first example:

B1 1+/
Min=+00000
Max=+01000
A=+01.00

B1 2+/
B=+00000
T=00:04s
P=2

Press

Use the and keys to navigate to the Min, Max, A, B, T
and P parameters. For each digit of a value, use the and

keys to scroll through value choices. Use the key to

navigate to the second screen from the last line of the first
screen, and the key to navigate from the top line of the

second screen to the first screen. Use the OK key to accept

changes.