IDEC FL1E SmartRelay User Manual

Page 174

Advertising
background image

IDEC SmartRelay functions

160

IDEC SmartRelay Manual

Backup of the real-time clock

The internal real-time clock of IDEC SmartRelay is buffered

against power failure. The buffering time is influenced by the

ambient temperature, and is typically 80 hours at an ambient

temperature of 25°C. If you are using the optional IDEC

SmartRelay Battery cartridge, or combined IDEC

SmartRelay Memory/Battery cartridge, IDEC SmartRelay

can retain the clock time for up to two years. To backup the

real time clock for more than 80 hours, insert a battery

cartridge or a combined memory/battery cartridge to the

base module.

Sample configuration

The output of an IDEC SmartRelay is to be set annually on

March 1, reset on April 4, set again on July 7, and reset again

on November 19. You need to configure two twelve-month

time switches with corresponding on-times. Then logically

link the outputs by means of an OR block.

B1 2+
ON :
YYYY–MM–DD
2000–03–01

B1 1+
Yearly = On
Monthly=Off
Pulse =Off

B1 3+
OFF :
YYYY–MM–DD
2099–04–04

B2 2+
ON :
YYYY–MM–DD
2000–07–07

B2 1+
Yearly = On
Monthly=Off
Pulse =Off

B2 3+
OFF :
YYYY–MM–DD
2099–11–19

Twelve-month
time switch 1
On-time Mar 1
Off-time Apr 4

Twelve-month
time switch 2
On-time Jul 7
Off-time Nov 19

On

Off

B1

B2

March 1
at 00:00 h

April 4
at 00:00 h

July 7
at 00:00 h

November 19
at 00:00 h