1 parameterisation dialog/signal flow, Parameterisation dialog/signal flow, 5motor control (mctrl) – Lenze 8400 HighLine User Manual

Page 155

Advertising
background image

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

155

5

Motor control (MCTRL)

5.4

V/f characteristic control (VFCplus)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.4.1

Parameterisation dialog/signal flow

Proceed as follows to open the dialog for parameterising the motor control:

1. »Engineer« Go to the Project view and select the 8400 HighLine controller.
2. Select the Application parameters tab from the Workspace.
3. Select the motor control from the Overview dialog level in the Motor control list field:

• "6: VFCplus: V/f linear" for linear characteristic or
• "8: VFCplus: V/f quadr" for square-law characteristic

More available V/f characteristic control modes:

• "10: VFCplus: U/f definable"

(from version 04.00.00 onwards)

.

With this motor control, the V/f characteristic can be freely defined.

Defining a user-

defined V/f characteristic

( 168)

• "11: VFCplusEco: V/f energy-saving"

(from version 10.00.00 onwards)

.

With this motor control, the motor is always operated in an optimal efficiency range via

a cosϕ control and the resulting voltage reduction (reduced copper losses in the

asynchronous motor).

V/f characteristic control - energy-saving (VFCplusEco)

( 172)

4. Click the Motor control V/f button to change to the OverviewMotor control V/f dialog

box.

• This dialog level only shows a simplified signal flow with the most important

parameters.

• When you click the >>More details button in the left-most position, a signal flow with

more details/parameters is displayed.