C00005 | application, C00006 | motor control, T in – Lenze 8400 HighLine User Manual

Page 800: C00006, C00005, If you, Ed in, Set in, Field, To se

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00005

800

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00005

C00006

Parameter | Name:

C00005 | Application

Data type: UNSIGNED_16

Index: 24570

d

= 5FFA

h

Selection of the technology application
Selection list

(Lenze setting printed in bold)

Info

0 Wiring has changed

This display appears if the FB interconnection has been

changed in the application level using the FB Editor.

1000 Actuating drive speed

This technology application is used to solve speed-

controlled drive tasks, e.g. conveying belts.

TA "Actuating drive speed"

1100 Actuating drive speed (AC Drive

Profile)

From version 13.00.00

This technology application is used to solve speed-

controlled drive tasks, e.g. conveying belts.

The process data word received by the master control is

interpreted as "AC Drive Profile" control word.

TA "Actuating drive speed (AC Drive Profile)"

2000 Table positioning

This technology application is used to solve position-

controlled drive tasks which are usually controlled by a

higher-level control system using a fieldbus.

TA "Table positioning"

3000 Switch-off positioning

From version 04.00.00

This technology application is used to solve speed-

controlled drive tasks which require a pre-switch off or

stopping at certain positions, e.g. roller conveyors and

conveying belts. This is implemented by connecting

switch-off sensors.

TA "Switch-off positioning"

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00006 | Motor control

Data type: UNSIGNED_8

Index: 24569

d

= 5FF9

h

Selection of the motor control mode

Motor control (MCTRL)

:

Select control mode

Selection list

(Lenze setting printed in bold)

Info

2 SC: Servo control ASM

This control type is used for the servo control of an

asynchronous motor.

• The control type requires a speed feedback via an

encoder mounted to the motor!

Servo control

3 SLPSM: Sensorless PSM

From version 10.00.00

This control type is used for the sensorless control of a

synchronous motor.

Sensorless control for synchronous motors

4 SLVC: Vector control

This control type is used for sensorless vector control of

an asynchronous motor.

• The control type requires motor parameters to be set

as exactly as possible!

Sensorless vector control

6 VFCplus: V/f linear

This control type is used for the speed control of an

asynchronous motor via a linear V/f characteristic and is

the simplest control type.

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f characteristic control

Advertising