2 PLC Program Transfer Function

28-32

WindO/I-NV2 User’s Manual

2.7 Precautions

• An error message is displayed if the PLC program file upload or download fails.

For details, refer to Chapter 35 “1.1 Errors Displayed on the Screen” on page 35-1.

• WindLDR Ver. 6.30 or later is required to create PLC program files.

• MICRO/I operation and PLC operation stops while the PLC program transfer function is running. After the PLC

program file upload or download is completed, the MICRO/I returns to the mode immediately before running the
PLC program transfer function and the PLC automatically starts running.

• Only passwords containing uppercase alphanumeric characters can be entered from the MICRO/I. When the PLC

password is configured with characters other than uppercase alphanumeric characters, the password cannot be
cleared.

• The PLC program transfer function cannot be run when the MICRO/I is in Simulation Mode. Switch to Run

Mode, Monitor Mode, or System Mode before running the PLC program transfer function.

• If a PLC program file exists with the same name in the save destination when uploading a PLC program file, the file

is overwritten with the uploaded file without displaying an overwrite confirmation message.

• While running the PLC program transfer function using a Key Button, Multi-Button, or Multi-Command, if a data

transfer function (project transfer, PLC program transfer, or file copy) is initiated, the only function that will work is
the currently running function. If two or more data transfer functions are configured to a Multi-Button or Multi-
Command, only the data transfer function displayed at the top of the function list on the parts property dialog box
is run.