Serial interface 2, O/i link interface, Micro/ i specif ication s – IDEC High Performance Series User Manual

Page 1321

Advertising
background image

WindO/I-NV2 User’s Manual

34-5

1 HG2G-S/-5S

34

MICRO/

I Specif

ication

s

Serial Interface 2

• Do not connect pin 6 (EN) with any other pins except when performing maintenance communications for

downloading project data.

O/I Link Interface

The HG2G-S/-5S Operator Interface can be connected to an O/I Link Unit for 1:N communication with a PLC. This
allows high-speed communication with the PLC host.

Interface Specification

RS232C

Connector

Mini DIN 8 pin

No.

Name

I/O

Function

1

RS

OUT

Request to Send

2

ER

OUT

Data terminal ready

3

SD

OUT

Send Data

4

RD

IN

Receive Data

5

DR

IN

Data set ready

6

EN

IN

Use set ready

7

SG

-

Signal Ground

8

NC

-

No connection