Serial interface 2, O/i link interface – IDEC High Performance Series User Manual

Page 1354

Advertising
background image

3 HG1F

34-38

WindO/I-NV2 User’s Manual

Communication Terminal Block (RS485/422 type: Model No.HG1F-SB22YF only)

Note that this terminal block cannot be used simultaneously with the D-sub connector.

Terminating Resistance Selector SW (RS485/422 type: Model No.HG1F-SB22YF only)

Setting the Terminating Resistance Selector SW to the ON side will insert and connect the terminating resistance

(330Ω) between RDA and RDB.

Serial interface 2

Do not connect pin 6 (EN) with any other pins except when performing maintenance communications for downloading

project data.

Connecting the maintenance communications cable to Serial interface 2 will stop the O/I Link communications.

O/I Link Interface

The HG1F Operator Interface can be connected to an O/I Link Unit for 1:N communication with a PLC. This allows

high-speed communication with the PLC host.

Connecting the maintenance communications cable to Serial interface 2 will stop the O/I Link communications.

Interface Specification

RS485/422

Connector

Terminal Block 5 pin

Recommended cable

0.3mm

2

Twisted-pair shielded cable

Conductor resistance: 85Ω/km maximum

Shield resistance: 20Ω/km maximum

No.

Name

Function

1

SDA

Send Data A

2

SDB

Send Data B

3

RDA

Receive Data A

4

RDB

Receive Data B

5

SG

Signal Ground

1

5

ON

OFF

Interface Specification

RS232C

Connector

Mini DIN 8 pin

No.

Name

I/O

Function

1

RS

OUT

Request to Send

2

ER

OUT

Data terminal ready

3

SD

OUT

Send Data

4

RD

IN

Receive Data

5

DR

IN

Data set ready

6

EN

IN

Use set ready

7

SG

-

Signal Ground

8

NC

-

No connection

6

3

4

7

8

5

2

1

Recommended cable

0.3mm

2

Twisted-pair shielded cable

Conductor resistance: 85Ω/km maximum
Shield resistance: 20Ω/km maximum