WindO/I-NV2 User’s Manual

3-83

6 Sub Host Communication

3

Communic

ation

Monitor the error information of each Station No.

These settings are for monitoring error information and control of each station number. To select a Device Address for
error information, go to the Device Manager. 256 word devices from top device set in Device Manager are used. Each
device is assigned to each station number of PLC.

• Bit 0: Connection

When this bit is 1, MICRO/I connect with each station. When this is 0, MICRO/I does not connect the station
number.
Default value is 1 when the station number is used.

• Bit 2: Finish 1st read

The value is changed to 1 when all devices assigned to the station number is read.

• Bit 4: Current error

This bit is changed to 1 while the communication error is occurred in any devices.
This bit is changed to 0 after the communication error is recovered.

• Bit 6: Error Log for reading

This bit is changed to 1 when the reading error has occurred in any devices.
This bit keeps 1 even if the communication error is recovered. This is changed 0 when clear bit is turn on.

• Bit 7: Error Log for writing

This bit is changed to 1 when the writing error has occurred in some devices.
This bit keeps 1 even if the communication error is recovered. This is changed 0 when clear bit is turn on.

Keep running with skipping the Station No. of communication error

When this setting is enabled, skip the station number error has occurred and connect with next station number.
MICRO/I retry communication with the error station number after other station number.
When this setting is disabled, retry communication with same station number until recover from the error.